Multiven Standard
Intake, discharge and recirculation in ventilation systems requiring high security: in air conditioning equipment, (air conditioning units, ventilation chambers, etc.), air conditioning systems (office buildings, call centers, department stores, hospitals, museums and airports, etc., industrial processes (pharmaceutical, food, optics, microelectronics industries, veterinary medicine, chemical industry and surface treatments) and as a pre-filter for Hepa and Ulpa filters.

Air Treatment
 

Quicktabs producto

Type: Compact Polyhedral Rigid Bag Filter.
Frame: Plastic (Polypropylene).
Filtering Element: Fiberglass paper.
Separators: Thermoplastic glue beads.
Sealant: Polyurethane.
Average Efficiency % (Em): 60% ≤ Em < 80%, 80% ≤ Em < 90%, 90% ≤ Em < 95% and 95% ≤ Em.
EN 779 Class: M6, F7, F8 and F9.
ISO 16890: ePM10 65%, ePM1 50%, ePM1 65% and ePM1 80%.
Recommended Final Pressure Loss: 450 Pa.
Temperature: 80ºC continuous service.
- LCC (EUROVENT CERTIFICATION) performance certification.
- Rigid construction, facilitating installation, all parts are Corrosion-proof and Incinerable.
- High nominal flow for low pressure loss: attained with a greater filter surface area in m2. with respect to bag filters.
- Water-repellent fiberglass filter media.
- Excellent performance in difficult operational conditions.
- High dust-retention capacity.
Reference Model Dimensions
HxLxP
Class
EN 779
ISO16890 Rated flow
(m3/h)

Inic.

PA.

Unit Vol.
(m3)
Weight
(Kg)

ME%

Energ.

classif.

Consume energy

Kwh/Year

UxP* Stock*
MVST242412F9 MVST 592x592x292 F9 ePM1 80% 3400 145 0,12 5,6 78 C 2300 1 S
MVST202412F9 MVST 492x592x292   ePM1 80% 2800   0,09 5,25   C   1 S
MVST122412F9 MVST 292x592x292   ePM1 80% 1700   0,06 3,3   C   1 S
MVST242412F8 MVST 592x292x292 F8 ePM1 65% 3400 115 0,12 5,6 71 C 1550 1 S
MVST202412F8 MVST 492x592x292   ePM1 65% 2800   0,09 5,25   C   1 S
MVST122412F8 MVST 292x592x292   ePM1 65% 1700   0,06 3,3   C   1 S
MVST242412F7 MVST 592x592x292 F7 ePM1 50% 3400 90 0,12 5,6 52 C 1280 1 S
MVST202412F7 MVST 492x592x292   ePM1 50% 2800   0,09 5,25   C   1 S
MVST122412F7 MVST 292x592x292   ePM1 50% 1700   0,06 3,3   C   1 S
MVST242412F6 MVST 592x592x292 M6 ePM10 65% 3400 70 0,12 5,6   C 1063 1 S
MVST202412F6 MVST 492x592x292   ePM10 65% 2800   0,09 5,25   C   1 S
MVST122412F6 MVST 292x592x292   ePM10 65% 1700  

0,06

3,3   C   1 S
UxP (*)
Units per box
Stock
F: Manufacturer, S: Stock, SL: Limited Stock
ME%: Minium Efficiency to EN779:2012
Energy Consumption,KWh/year: Calculated according
to Eurovent Guideline 4/21-2014

Energy Class: Calculated according to Eurovent RS4/C/001-2017

 

FUNCTION OF PRESSURE DROP VS. FLOW RATE
  • MULTIVEN ST