true
MULTIVEN ES A+
Multiven SAVE ENERGY features highly-efficient filtration with extremely LOW ENERGY CONSUMPTION A+. Air conditioning systems (Hospitals, laboratories, museums, aiports, etc.). Industrial processes (pharmaceutical, food, optics, micro-electronics, veterinary services, chemical and surface treatment industries).

Air Treatment
 

Quicktabs producto

Type: Compact filter with rigid multi-dihedral rigid bags.
Frame: ABS.
Filtering Element: Fiberglass sheet.
Separators: Hot melt adhesive strands.
Sealant: Polyurethane.
Average efficiency % (Em): 80% ≤ Em < 90%, 90% ≤ Em < 95% and 95% ≤ Em.
EN 779 Class: F7, F8 and F9.
ISO 16890: ePM1 50%, ePM1 65% and ePM1 80%.
Recommended Final Pressure Drop: 450 Pa.
Temperature: 80ºC continued service.
- ENERGY SAVING (Extremely Low Energy Consumption A+).
- LCC (EUROVENT CERTIFICATION) performance certification.
- Extended Working (replacements required less often).
- Rigid construction, facilitating installation, all parts are Corrosion-proof and Incinerable.
- High nominal flow for low pressure loss: attained with a greater filter surface in m2.
with respect to bag filters.
- Water-repellent fiberglass filter media.
- Extremely high dust-retention capacity.

 

Reference Model Dimensions
H x B x P
Class
EN 779
ISO16890 Rated Flow
(m3/h )

Inicial Pa

Unit VOl.
(m3)
Weigth
(Kg)

ME

%

Energy Class

Consume energy (Kwh/year)

UxP* Stock*
MVES242412F9 MVES 592x592x292 F9 ePM1 80% 3400/4250 95 0,11 6,9

73

A+ 1196 1 F
MVES202412F9 MVES 492x592x292   ePM1 80% 2800/3500   0,09 6,4   A+   1 F
MVES122412F9 MVES 292x592x292   ePM1 80% 1700/2125   0,06 3,8   A+   1 F
MVES242412F8 MVES 592x592x292 F8 ePM1 65% 3400/4250 88 0,11 6,9 57 A+ 954 1 F
MVES202412F8 MVES 492x592x292   ePM1 65% 2800/3500   0,09 6,4   A+   1 F
MVES122412F8 MVES 292x592x292   ePM1 65% 1700/2125   0,06 3,8   A+   1 F
MVES242412F7 MVES 592x592x292 F7 ePM1 50% 3400/4250 73 0,11 6,9 38 A+ 795 1 F
MVES202412F7 MVES 492x592x292   ePM1 50% 2800/3500   0,09 6,4   A+   1 F
MVES122412F7 MVES 292x592x292   ePM1 50% 1700/2125   0,06 3,8   A+   1 F
UxP (*)
Units par box
Stock
F: Manufacturer, S: Stock, SL: Limited Stock
ME%: Minium Efficiency to EN779:2012
Energy Consumption,KWh/year: Calculated according
to Eurovent Guideline 4/21-2014

Energy Class: Calculated according to Eurovent RS4/C/001-2017

 

FUNCTION OF PRESSURE DROP VS. FLOW RATE
  • F9
  • F8
  • F7
MINIUM EFFICIENCY TEST
  • F9
  • F8
  • F7